High Temperature Limit Control
Figure 36. LOW LEVEL CONTROL

Operating, Maintenance And Repair Parts Instructions Heater, Hot Oil, Trailer Mounted Page Navigation
  57    58    59    60    61  62  63    64    65    66    67  
img
Figure 35. LOW LEVEL CONTROL MOUNTING.
MOUNTING:
The low level control has a 21/2" pipe thread and is mounted into a 21/2" pipe coupling welded into
the expansion tank. In mounting the control to the tank, the hex nut should be turned so that the
1/2 " conduit opening is at the top in a horizontal plane. The float must move up and down in a
vertical plane.
OPERATING:
The dual switches are activated by movement of the float ball. When the ball rises, the top switch is
closed; when the ball falls the switch opens. This is controlled by the heat transfer oil level. The second
switch is not used. It is left disconnected.
SWITCHING:
The switch designations are 1 & 2 and 3 & 4. On a rising level, 1 & 2 close with 3 & 4 opening.
SWITCH RATING: 115V.A.C. .......- 7.4 Amps.
230 V.A.C. -.......- 3.7 Amps.