Figure 38. ULTRAVIOLET (U.V.) CELL.
54. Ignition Transformers and Bussbars
a.
Removal. Refer to Fig. 39 and remove the ignition transformer and ignition cables.
WARNING: DO NOT SERVICE ANY ELECTRICAL EQUIPMENT WHILE ELECTRICAL SUPPLY IS
CONNECTED. TURN ALL ELECTRIC POWER OFF. IGNITION TRANSFORMER HAS 120
VOLTS PRIMARY CONNECTIONS, WITH 10,000 VOLTS SECONDARY TO GROUND.
1.
Remove 2 screws on ignition transformer; tag and disconnect electrical wires, remove electrical fittings.
2.
Remove 2 screws from burner cover plate; remove plate.
3.
Pull ignition wires from ignition transformer.
4.
Remove 2 nuts from mounting studs; remove ignition transformer.
73