TM 9-2540-207-14&PE4 - REVERSE BURNER AIR FLOWE4Burner Fan is measuring reverse air through the heater, or is operating out of rangeCHECK/POSSIBLE CAUSEREF.REPAIR1Check that ducting of the2.2Reconnect combustion air ducting correctlycombustion air system to theRestart Heaterinlet and the exhaust ductingare correctly attached to theheater2Check that Combustion air andRemove obstructionsexhaust ducting is free fromRestart Heaterobstructions3Check for carbon accumulation5.3Remove carbon and clean Combustionor obstructions in CombustionAssemblyAssemblyRestart HeaterCheck condition of Flame Tube5.3.2If distorted, replace Flame Tube ANDand Burner Chamber5.3.5Burner ChamberRestart Heater4Defective Burner Fan5.5.4Replace Burner Fan PlateRestart Heater5Defective Heat Exchanger5.4.1Replace Heat ExchangerRestart Heater6Defective Electronic5.2.5Replace Electronic Programmed ControllerProgrammed Controller BoardRestart Heater6-18